SO-210313I / 1Ph 32A / 7.36kW / 21 x C13, 3 x C19 / 2 x 16A

Key Advantages
  • Reliable Power Distribution for Critical Infrastructure
  • Real-Time Monitoring with Intelligent Management
  • Flexible OEM and ODM Customization Support
  • High-Efficiency Solutions for Modern Data Centers
  • Strict Quality Control with Global Certifications
1. General Information
1.1  Rated Input Voltage ~230V 1P+N+E, 50–60Hz
1.2  Operating Voltage Range ~176–264V
1.3  Rated Current 32A
1.4  Maximum Power 7.36kW
1.5  Total Number of Outlets 21 x C13, 3 x C19
1.6  Outlet Retention TypeMechanical retention with push-button release
1.7  Control Type Per Outlet
1.8  Monitoring Type Per Outlet, Outlet Groups
1.9  Form Factor 0U Vertical
1.10  Overall Dimensions (H × W × D / D max) 1830 × 56 × 52mm
1.11  Distance Between Mounting Brackets (Peg-Tool) 1244mm
1.12  Standard Warranty 2 years
1.13  Extended Warranty Up to 5 years

 

2. Electrical Characteristics
2.1  Rated Input Voltage ~230V 1P+N+E, 50–60Hz
2.2  Operating Voltage Range ~176–264V
2.3  Rated Current 32A
2.4  Rated Neutral Current 32A
2.5  Maximum Power 3.68kW
2.6  Input Position Top Entry
2.7  Connection Type IEC 60309 32A Plug, 1P+N+E
2.8  Overcurrent Protection TypeHydraulic-magnetic circuit breakers with trip-free mechanism
2.9  Number of Circuit Breakers 2 × 16A, 1P
2.10  Circuit Breaker Rated Current 16A
2.11  Breaking Capacity (Icu/Ics) Icu 6 kA, Ics 6 kA
2.12  Breaker Poles 1P
2.13  Power Cable Length 3 m
2.14  Cable Insulation Type PVC, flame retardant, IEC 60227
2.15  Cable Cross-Section 3 × 6.0mm²
2.16  PDU Self-Consumption No more than 26W
2.17  Grounding Integrated + redundant on chassis (M5 stud)

 

3. Outputs and Outlets
3.1  Total Number of Outlets 21 x C13, 3 x C19
3.2  Outlet Rated Voltage ~230V
3.3  Outlet Rated Current 16A
3.4  Maximum Outlet Output Power 3680W
3.5  Outlet Retention TypeMechanical retention with push-button release
3.6  Outlet Retention Force No less than 100N (10kg)
3.7  Outlet Status Indication LED indication
3.8  Outlet Numbering Order Top to Bottom
3.9  Locking Cable Support Yes
3.10  Number of Outlet Groups (Physical) 2 groups
3.11  Per-Outlet User Access Restriction Supported
3.12  Number of Outlet Groups (Logical) Up to 8 groups (configurable)
3.13  Control Type Per Outlet

  

4. Monitoring and Measurements
4.1  Monitoring Type Per Outlet, Outlet Groups
4.2  Measured Electrical Parameters A, VA, kVA, kWh, PF
4.3  Measurement Accuracy ±1%
4.4  Current Measurement Resolution 0.01 A
4.5  Power Measurement Resolution 0.1W
4.6  Temperature and Humidity Measurement Supported (external sensor)
4.7  Door Open Monitoring Supported (external sensor)
4.8  Supported External SensorsTemperature, humidity, smoke, flood, door open
4.9  Minimum Data Update Interval 1sec
4.10  Data Logging Interval 10sec–60min (configurable)
4.11  Non-Volatile Event Log Yes
4.12  Event Log Capacity5MB, auto-cleanup of first 1000 records when full
4.13  History Retention Period No less than 18 months
4.14  Email Notifications Supported
4.15  SNMP Trap Notifications Supported
4.16  Syslog Notifications Supported, UDP 514
4.17  Threshold and Alert Configuration Supported
4.18  RTC Battery Present Yes
4.19  Hot-Swap Monitoring Module Supported
4.20  Power Section Protection During Module Replacement Yes
4.21  PDU Display LCD 2.0″, 240×320, backlit
4.22  Display Orientation Adjustment Supported
4.23  Ethernet Port 1× RJ45 10/100 Mbps
4.24  USB Port USB 2.0 Type A
4.25  External Sensor Ports3 × RJ-type (temperature, humidity, door open)
4.26  External Sensor Expansion Module Port 1 × RJ-type
4.27  Serial Port 1 × RJ-type (RS-232)
4.28  Controls 3 functional buttons
4.29  Reset Button Yes, hardware
4.30  Monitoring Module Status Indication Yes, LED

  

5. Connectivity and Security
5.1  Cascade Connection Supported, 32 – Modbus, 10 – SNMP
5.2  IPv4 Support Yes
5.3  IPv6 Support Yes
5.4  DHCP Client Yes
5.5  Static IP Address Configuration Supported
5.6  Web Management Interface HTTP / HTTPS
5.7  HTTPS Encryption TLS 1.2 / 1.3
5.8  Custom TLS Certificate Upload Supported, PEM/PKCS#12
5.9  CLI Interface SSH / Telnet
5.10  Insecure Protocol Disabling Supported
5.11  User Role and Permission Configuration Supported
5.12  Number of Local Users Up to 10 users
5.13  Password Security Policy Configuration Yes (complexity, expiration)
5.14  SNMP Support v1 / v2c / v3
5.15  Modbus Support Modbus-TCP/RTU
5.16  RADIUS Support Yes
5.17  NTP Time Synchronization Supported
5.18  Remote Log Export Supported, Syslog
5.19  Remote Firmware Update Supported, Web
5.20  Configuration Backup Supported

  

6. Construction and Installation
6.1  Form Factor 0U Vertical
6.2  Distance Between Mounting Brackets (Peg-Tool) 1244mm
6.3  Overall Dimensions (H × W × D / D max) 1830 × 56 × 52mm
6.4  Side Mounting Option Supported
6.5  Side Mounting Kit Yes, side mounting kit with 90° rotation
6.6  Enclosure Protection Rating IP20
6.7  Enclosure Material Steel
6.8  Enclosure Color Black, RAL (optional)

  

7. Operating Conditions and Reliability
7.1  Ambient Operating Temperature 0…+60 °C
7.2  Operating Relative Humidity 5–95% non-condensing
7.3  Mean Time Between Failures (MTBF) No less than 100,000 hours
7.4  MTBF Calculation Method MIL-HDBK-217F
7.5  Allowable Continuous Load 100% of Rated
7.6  Shock Resistance IEC 60068-2-27
7.7  Surge Current Resistance IEC 61000-4-5
7.8  Overload Resistance 125% for 1sec
7.9  Electrostatic Discharge (ESD) Immunity IEC 61000-4-2 (±8kV, contact)
7.10  Electromagnetic Interference (EMC) Immunity IEC 61000-4 series

  

8. Certifications and Compliance
8.1  Electrical Safety Standard IEC 61010-1, IEC 61010-2, IEC 62368-1
8.2  Electromagnetic Compatibility (EMC) IEC/EN 55032, IEC/EN 55035TR
8.3  EAC Compliance (EAEU) CU 004/2011, TR CU 020/2011
8.4  RoHS Compliance Yes

  

Note: Specifications are subject to change without prior notice.